4.4 Description of the units
4 Function description
6
The PSENvip ends communication.
All outputs are set = 0:
Activate = 0
Acknowledge PSENvip -> PLC = 0
Tool class PSENvip -> PLC Bit 1 = 0
Tool class PSENvip -> PLC Bit 2 = 0
7
The safety system ends communication.
PLC Ready = 1/0 pulse edge
Tool class PLC -> PSENvip Bit 1/2 = 0 or 1, depending on the orig-
inal status
Tool class
123
Tool class PLC -> PSENvip Bit 1 0 1 1
Tool class PLC -> PSENvip Bit 2 1 0 1
INFORMATION
The requirements of the user program in the safety system are
described under "System Connections".